TeSys D contactor data reference table
3-pole contactors - Motor control up to 75 kW at 400 V, in category AC-3
Standard power ratings of 3-phase motors 
50-60 Hz in category AC-3
(θ y 60 °C)
Rated 
operational 
current 
in AC-3 
440 V
up to 
Instantaneous 
auxiliary 
contacts
Basic reference, 
to be completed by adding 
the control voltage code
220 V
230 V
380 V
400 V
415 V 440 V 500 V 660 V 
690 V
1000 V Fixing (1)
kW  kW kW kW  kW  KW kW  A  
Connection by screw clamp terminals
2.2 4 4 4 5.5 5.5 9 1 1 LC1D09
3 5.5 5.5 5.5 7.5 7.5 12 1 1 LC1D12
4 7.5 9 9 10 10 18 1 1 LC1D18
5.5 11 11 11 15 15 25 1 1 LC1D25
7.5 15 15 15 18.5 18.5 32 1 1 LC1D32
9 18.5 18.5 18.5 18.5 18.5 38 1 1 LC1D38
Power connections by EverLink® BTR screw connectors (2) and control by screw clamp terminal
11 18.5 22 22 22 30 40 1 1 LC1D40A
15 22 25 30 30 33 50 1 1 LC1D50A
18.5 30 37 37 37 37 65 1 1 LC1D65A
22 37 37 37 37 37 66 1 1 LC1D80A
Connection by screw clamp terminals or connectors
22 37 45 45 55 45 45 80 1 1 LC1D80
25 45 45 45 55 45 45 95 1 1 LC1D95
30 55 59 59 75 80 65 115 1 1 LC1D115
40 75 80 80 90 100 75 150 1 1 LC1D150
Connection by lugs or bars
In the references selected above, insert a figure 6 before the voltage code.
Example: LC1D09 becomes LC1D096.
Standard control circuit voltages (for other voltages, please consult your Regional Sales Office)
a.c. supply
Volts 24  42 48 110 115 220 230 240 380 400 415 440 500
LC1D09…D150 (D115 and D150 coils with built-in suppression as standard, by bi-directional peak limiting diode).
50/60 Hz B7   D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7 S7
LC1D09…D65 (not available with "connection for lugs or bars")
50 Hz B5   D5 E5       P5            
LC1D80…D115
50 Hz B5 D5 E5 F5 FE5 M5 P5 U5 Q5 V5 N5 R5 S5
60 Hz B6 E6 F6 M6 U6 Q6 R6
d.c. supply
Volts 12 24 36 48 60 72 110 125 220 250 440    
LC1D09…D38 (coils with integral suppression device fitted as standard, by bi-directional peak limiting diode)
U 0.7…1.25 Uc JD BD CD ED ND SD FD GD MD UD RD    
LC1D40A …D65A (coils with integral suppression device fitted as standard, by bi-directional peak limiting diode)
U 0.75…1.25 Uc JD (3) (3) (3) (3) (3) (3) (3) (3) (3) RD    
LC1D80…D95
U 0.85…1.1 Uc JD  BD CD ED ND SD FD GD MD UD RD    
U 0.75…1.2 Uc JW BW CW EW SW FW MW    
LC1D115 and D150 (coil with built-in suppression device as standard)
U 0.75…1.2 Uc –  BD ED ND SD FD GD MD UD RD    
Low consumption DC (for low consumption AC/DC: Deca green contactors)
Volts 5   12 20 24 48 110 220 250          
LC1D09…D38 (coils with integral suppression device fitted as standard, by bi-directional peak limiting diode)
U 0.8…1.25 Uc AL  JL ZL BL EL FL ML UL          

 

(1) LC1D09 to D80A: clip-on mounting on 35 mm rail NSYSDR or screw fixing.
LC1D80 to D95 ac: clip-on mounting on 35 mm rail NSYSDR or 75 mm 5 rail AM1DL or screw fixing.
LC1D80 to D95 dc: clip-on mounting on 75 mm rail AM1DL or screw fixing.
LC1D115 and D150: clip-on mounting on 2 x 35 mm rails NSYSDR or screw fixing.

(2) BTR screws: hexagon socket head. In accordance with local electrical wiring regulations, a size 4 insulated Allen key must be

(3) For these coil voltages, choose from Deca green contactors. Same product ref. radical, just add BBE coil voltage code for 24 V
DC, BNE for 24-60V AC/DC, EHE for 48-130 V AC/DC, KUE for 100-250 V AC/DC. Exemple: LC1D40ABBE.